Quick answerXLPE cable runs hotter and carries more current than PVC cable of the same size, so it is the usual choice for main power feeders and for all HT cable. PVC cable costs less and suits lighter duty LT circuits, control wiring and building wiring.
Comparison
| Point | XLPE cable | PVC cable |
|---|---|---|
| Insulation | Cross-linked polyethylene | Polyvinyl chloride |
| Maximum conductor temperature in service | 90 °C | 70 °C |
| Maximum temperature during short circuit | 250 °C | 160 °C |
| Current capacity, same size | Higher | Lower |
| Voltage range | LT and HT | Mostly LT |
| Moisture and chemical resistance | Better | Good |
| Cost | Higher | Lower |
| Indian Standard (LT) | IS 7098 Part 1 | IS 1554 Part 1 |
When to choose XLPE
- Main and sub-main feeders, transformer and motor feeders
- Any cable above 1.1 kV
- Hot locations, or where a smaller cable size saves tray space
When to choose PVC
- Control cables and light LT distribution
- House and panel wiring
- Short runs where the load is well within the cable rating
Frequently Asked Questions
For power cables, usually yes: it carries more current and withstands faults better. For wiring and control circuits PVC is adequate and cheaper.
Generally yes, for the same size and voltage grade. Going the other way needs a check, because PVC carries less current.
Most do. XLPE is the insulation on each core; the outer sheath is commonly PVC.
Tell us the size, cores and voltage grade and we will quote XLPE or PVC cable in your approved make. See our electrical cables and conductors supply.