Cable Size Calculator as per Load

Enter the load in kW, the supply voltage and the power factor to get the full load current. Then choose the cable size whose current rating is above that figure, and check the voltage drop for long runs.

1

Load details

Full load current

0 A

-

Supply-
Load-
Voltage-
Power factor-
Get a quote for this cable

Your entries are carried into the message.

Engineering note: This gives the load current only. Select the cable size from the manufacturer's current rating chart for your cable type and laying method, after derating.

How to Size a Cable for a Load

Three steps, from load current to a size you can confirm with your engineer.

Step 1: Find the load current

Use the calculator above, or the formulas.

Three phase: current (A) = kW × 1000 ÷ (1.732 × voltage × power factor)

Single phase: current (A) = kW × 1000 ÷ (voltage × power factor)

Worked example: a 30 kW three phase load at 415 V and 0.8 power factor draws 30,000 ÷ (1.732 × 415 × 0.8) = 52.2 A.

Step 2: Select the size from the rating chart

From the manufacturer's catalogue.

Choose the smallest cable whose current rating, after derating, is higher than the load current. Ratings differ for copper and aluminium, for PVC and XLPE, and for cable laid in air, in ground or in duct.

Use the current rating chart in the catalogue of the make you plan to buy. Share your load current with us and we will help you shortlist a size.

Step 3: Check voltage drop on long runs

Go up one size if the drop is too high.

Voltage drop (V) = current × length in metres × the cable's mV per amp per metre figure ÷ 1000

The mV per amp per metre figure is listed beside each size in the manufacturer's catalogue. If the drop exceeds the limit your project specification allows, go up one size.

Frequently Asked Questions

About sizing cables for a load.

First find the current, 52.2 A at 415 V and 0.8 power factor. Then pick the size from the manufacturer's rating chart for your cable type and laying method, and confirm it against the motor starting requirement.

Heat is the limit. A cable in free air cools better than one buried or grouped with others, so its rating is higher.

No. It is an estimate for enquiry and budgeting. Final sizing belongs to your electrical engineer or consultant.